Summary Results
The demonstration was a success as the units now provide colder supply air with greater efficiency due to the restoration of the heat transfer ability of the evaporator and condenser coils, both of which have a direct correlation to an increase in the number of tons the machines are now capable of producing. This means the systems reach set point faster and shut off sooner thereby saving energy.
Total system efficiency across the two units improved by an average of 14.3%, while the EER across the units rose by 15.4%. There was an overall increase in coil capacity of 13,140 Btu’s, equating to the restoration of 1.1-tons of capacity or 12.6%. There is also a reduction of 13.3% in kW/ton, which is another measurable way to view the thermodynamic enhancement brought about by the ECM.

5-Ton System Test Data


4-Ton Split System Data


Energy Efficient Technologies worked with Crescent Crown to reduce energy usage and Scope 2 Carbon Footprint in all of their locations in all machines. In all EET deployed CryoGenX4 in 141 Large...
The Manufacturer of CryoGenX4 oversaw validations for Reefers in South Africa. A single reefer trailer was tested sucessfully with 42% improvement in pull down times due to CryoGenX4 making it colder...
Wendy's did a 2 year independent study in 10 stores across 24 RTU's and 20 refrigeration systems on the previous generation of HVAC optimization due to oil fouling. In 2013 following the successful...