Price Chopper Grocery New York

A grocery chain looking to be more sustainable and save costs:

Price Chopper grocery was interested in saving costs and reducing carbon footprint. Energy Efficient Technologies suggested optimizing HVAC and refrigeration with what is now called CryoGenX4.

We figured it out:

Our Energy Efficient Technologies team performed a savings validation evaluation for Price Choppers of CryoGenX4 in their refrigeration systems.

• Dates: Power metering began on 17 Jan 2016 and ran through 10 May 2016. Current transformers captured all the power used on all compressors making up the three refrigeration racks, as well as the associated condensing units for these systems.
• Objective: Testing was conducted to demonstrate that the HVAC and refrigeration Energy Control Measure (ECM) [now called CryoGenX4]would reduce overall energy use of the refrigeration system by 8% or more through the combined restoration of thermal efficiency and capacity at each of 63 individual evaporators connected to the system inside the store and the 14 compressors comprising the three separate rack systems.
• Testing Conditions: It was agreed to in advance that all testing was to be conducted with the equipment operating “as-is”. Since this was an “in-situ” test, to eliminate as many variables as possible, it was also agreed to in advance that only the power meter data from periods where the outside weather conditions were the same in both the baseline and post collection periods would be used to determine any energy savings achieved. These conditions have a great effect on the operational performance and overall power consumption of the refrigeration system. The in-store logger positioned near the seafood case in the rear of the store showed the conditions inside the store remained constant throughout the entire test period. In this test we did not track the load on the evaporators that include things like inventory arrivals, stocking of coolers/freezers, numbers of customers, etc.

Here’s the results:

  • 23% reduction in energy costs
  • 14 month Payback
  • Return on Investment over the life of the equipment = 951.5%
    12 Hour Energy Savings Comparison


    Results show a substantial reduction in average amount of current, KW and VA (Demand)
    required to operate the refrigeration system under identical outdoor weather conditions
    and consistent In Store conditions between the busiest store hours of 10AM 6PM.
    Baseline vs Post Under Identical Weather Conditions During Busiest Store Times

Related Case Studies

Washco Properties Shopping Malls

Since 2014 Energy Efficient Technologies has performed energy audits and upgraded dozens of strip malls and office building locations to LED for Washco Properties across Maryland and Pennsylvania.

KRM Development Maryland

Energy Efficient Technologies has been upgrading KRM Development Corporation facilities to reduce carbon footprint and energy bills since 2015 in numerous locations. KRM Development Corporation is a...

MillerCoors- Crescent Crown Distributing

Energy Efficient Technologies worked with Crescent Crown to reduce energy usage and Scope 2 Carbon Footprint in all of their locations in all machines. In all EET deployed CryoGenX4 in 141 Large...

EET Logo

Energy Efficient Technologies
400 East Pratt Street, Suite 800
Baltimore, MD 21202

800-344-8132 (Office)

Connect On Social