Tojo Mushroom

Tojo Mushroom-Food Manufacturer Pennsylvania

Building bird's eye view

Tojo Mushroom was looking to save costs and reduce their carbon footprint.

Energy Efficient Technologies performed a detailed energy audit, made numerous recommendations for improvements.

The purpose of this case study is to provide the results of the savings validation pilot of an HVAC and refrigeration ECM now known as CryoGenX4 at the largest mushroom growing facility in the US

Operation of the Mushroom House

Each HVAC unit used for conditioning the mushroom house operates on a unique schedule of set points, percentage of outside air, backup A/C, and heat at 100% while A/C is on.  This schedule is important as the operation of the equipment affect the results of the test.

Data Analysis

The data was analyzed by gathering the operation schedule of each unit and categorizing similar settings of set point, outside air percentage, and outside temperature.  Using multiple similar days the percentage of savings before and after were created and averaged to present a final value.

Results

  • Unit#17 shows an energy savings of 33%
  • Unit#19 shows an energy savings of 28%.
  • This represents a simple payback of approximately  1.55 Years. 
  • Return on Investment over equipment lifetime = 862%

Other Food Manufacturing Case Studies:

Related Case Studies

Marriot Residence Inn Miami

Marriott Residence Inn Miami Airport Detailed baseline and post measurements were taken of six (6) nominal 10-ton, 4-yr old AAON Roof Top Heat Pump Units (RTUs) serving the hotel. The primary purpose...

Meals on Wheels Baltimore, MD

The Sustainability group in the City of Baltimore government asked Energy Efficient Technologies to assist in deploying technology to reduce carbon footprint and utility bill costs. One of these...

Kraft

In 2023, the manufacturer of CryoGenX4 with careful coordination and logistical support from the Engineering Team at the Kraft-Heinz plant in San Jose, Costa Rica, began a chiller performance...

EET Logo

Energy Efficient Technologies
400 East Pratt Street, Suite 800
Baltimore, MD 21202

800-344-8132 (Office)

Connect On Social