Starbucks- DPI Distributor

Case Study Summary: CryoGenX4 Increases Efficiency and Reduces Energy Costs for DPI- A Starbucks Distributor

dpi rooftop refrig

Client: Starbuck's distributor, DPI Mid-Atlantic Operations, Capitol Heights, MD
Testing Dates: October 2019
Tested System: Refrigeration unit

CryoGenX4, an energy control measure (ECM), was tested on DPI's refrigeration system #7, which had lost efficiency due to oil fouling over three years of operation. The technology restored performance by cleaning heat exchange surfaces and preventing future oil buildup, resulting in significant improvements.

Key Results:

  • Capacity Increase: The system's cooling capacity increased by 17.8%, from 13.69 tons to 16.12 tons, restoring nearly all of its original capacity.
  • Efficiency Gains: Energy efficiency improved by 16.6%, reducing energy consumption from 3.2 kW/ton to 2.67 kW/ton.
  • Financial Impact: DPI saved $5,381 annually in energy costs per unit, leading to an estimated ROI >1000%.
  • Environmental Benefit: Each unit treated will reduce 36.2 metric tons of greenhouse gases annually over its lifetime, further supporting sustainability goals.

Why It Matters: CryoGenX4 helps refrigeration and HVAC systems operate more efficiently, reducing energy costs, extending equipment life, and cutting carbon emissions—all with a quick ROI.

  40 Distribution Centers & Reefers- Business Case 
Lifetime Savings  $         51,880,943
Building Value Increase @ 6.25% Cap Rate  $         20,972,808
Investment After Tax Deduction  $           3,788,729
11 Year ROI (Electricity Savings Only) 2365%
Approximate kWh Reduced  351 Million kWH 

CryoGenX4 to the Rescue

The decision to use CryGenX4 yielded impressive results. When initially tested, the refrigeration system #7 was producing 13.69 tons of its designed 16.7 tons of cooling capacity.

Just three days after implementing the CryoGenX4 ECM:

dpi results chart

What once took the refrigeration system 20 minutes of runtime to satisfy its set point prior to being treated, it accomplished the same task in 16 1⁄2 minutes.

Less time running translates directly into lower utility costs, fewer repairs and longer life.

CryoGenX4 projected savings for DPI were:

  • Return on investment over equipment lifetime- 2937%
    DPI BMS system
    dpi ice compressor
  •  
  • dpi meters

 

Related Case Studies

Houchens Industries Price Less Grocery

In 2024 Houchens Industries contracted with Energy Efficient Technologies to validate the savings and carbon footprint reductions for their 400 grocery store chain. Method 1: Below are the results of...

Tailored Brands/Men's Wearhouse

Men’s Wearhouse/Tailored Brands, Houston TX Dressed for Success This facility in Texas was experiencing lost capacity and decreased performance in 125 25-ton rooftop units that occurred over a period...

PIZZA HUT, BALTIMORE MD

Our client, Pizza Hut of MD, operates 48 locations. Energy Efficient Technologies began working with a Baltimore Pizza Hut in 2008, installing 175 sensors to capture all operational and energy data...

EET Logo

Energy Efficient Technologies
400 East Pratt Street, Suite 800
Baltimore, MD 21202

800-344-8132 (Office)

Connect On Social